Analysis of Protection System on Three-phase Induction Motor PT South Pacific Viscose
Abstract
This paper describes the three-phase induction motor protection system used in PT South Pacific Viscose. The induction motor studied is a motor with a power of 90 kW. The nominal current obtained from the calculation is 151.934 A. Protection system in the form of MCCB and TOR. From the results of the calculation of the MCCB rating that must be used 379.835 A and the TOR rating of 189.917 A, while the installed MCCB is 400 A and TOR 200 A. By comparing the results of calculation observations with the field, it can be concluded that the use of the protection system is appropriate.
References
, P. (2000). General Requirements for Electrical Installation 2000 (PUIL 2000). Jakarta: Director General of Electricity.
Darma, S. (2019). Analysis of 3 Phase 37 Kw Electric Motor Protection as a Press Machine Driver. Palembang University Faculty of Engineering, 1-11.
Hartono, Praharto, Y., & Fitrizawati. (2020). Analysis of Thermal Overload Relay (TOR) Type Lrd08c in 3 Phase Belt Conveyor Motor Protection Systems. ITEKS, 12(2), 80-81.
Novriandi, D., Zakri, A. A., & Ervianto, E. (2019). Sag and Tension of 275 kV Transmission Line using Catenary. International Journal of Electrical, Energy and Power System Engineering (IJEEPSE), 2(3), 15.
Putra, I. M. (2017). Evaluation of Motor Control Center (MCC) Panel Design for Wastewater Treatment Plant (WWTP) at PLTMG Duri-Riau. Malang: Brawijaya University.
Stevenson, J. W. (1998). Elements of Power System Analysis. Jakarta: Erlangga.
Sumanto. (2013). Elements of Power System Analysis. 2013: Andi Offset.
Sutiyanto. (2018). Design of a Three-Phase Motor with Two Speeds Using Changes in the Number of Poles.
Tiyono. (2017). Design of Overcurrent Protection Relay Settings in Industrial Electric Motors. Jurnal Transmisi, 15 (1), 41-43.
Zuhal. (1998). Fundamentals of Electrical Power Engineering and Power Electronics. Jakarta: Gramedia.